single-phase-ups

10 KVA Online UPS

(Harsh 10.0 KVA 60 MINUTE (Three Phase Input & Single Phase Output) ONLINE UPS INDICATIVE MADE IN INDIA OEM BIS REGISTERED MANUFACTURE)

Generic
Rating in KVA10.0 KVA
TechnologyIGBT-PWM without inbuilt isolation transformer
Input PowerThree phase 300 V - 450V sinewave,50Hz
Output powerSingle phase 230V +/-1% sinewave 50 Hz
Backup time (Minutes)60
Minimum VAH (VAH) 16000
Warranty for UPS (Years)1
Movable Trolley for BatteriesWithout trolley but with rack
Warranty for battery 1 Year
Degree of ProtectionIP21
Cabling 5 meters for input and out put Without
Paralleling kit for synchronising Without
Installation and Commissioning Yes
Constructional
Minimum thickness of M.S.Sheet Enclosure duly painted (mm)1.2
Type of BatterySMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Functional
Maximum overshoot and Under shoot of output rated voltage4
Voltage Regulation from no load to full load (%)< / = 3%
20% Overload limit for minimum 10 minutes Yes
Overall Efficiency (%) >/=90%
Total Harmonic Distortion(THD) (%)Maximum 3%
50% Overload limit for minimum 1 minutesYes
Protection
Protection for under voltage at battery terminal at 10.5V per 12 V batteryYes
Protection of Over voltage,Short Circuit & over load at UPS output terminalYes
Metering And Indications
Digital Metering in UPS for AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage and Current Yes
Indicators for mains presence,Battery charging and discharging,Output Over Load, Low Battery Voltage Yes
Reports And Certification
Damp Heat : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C,two cycles of (12+12) hours each 2007) Yes
Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes
Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes
Availability of the Type Test Report from Central Govt. /NABL/ILAC Accredited lab covering all technical requirements. Yes
Type Test Certificate No. 81001295
Type Test Certificate date Jan-2017
Name of Lab Bis Registered
Address of Lab Delhi
As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes

The company's main aim has always been to serve customers by providing excellent and reliable power conditioning solutions.

About us

Founded in 1990, Harsh Industries is today, the No.1 Indian Power Electronics Company. We design, manufacture and supply of a full range of power conditioning & power back-up products, services and solutions – Online UPS, Industrial Inverters, Solar Inverters, Industrial Systems, Stabilizers, Isolation Transformers, Active Harmonic Filters, Static Transfer switches and customized power electronic solutions.

Contact us